کد کالا : FDR-C
ساخت : 0
گارانتی : 0
اصالت کالا : 0
FDR-C Blasting & Painting Dehumidifier:
FDR-C Blasting & Painting Dehumidifier is the dedicated equipment for blasting & painting in heavy industry. It is widely applied in large equipment manufacturing industry such as automobile, shipbuilding. With its solid structure, easy to maintain, large dehumidification capacity feature, it can be used in high temperature & humidity costal environment. Configuring international famous brand screw or scroll type compressor and high performance silica gel desiccant wheel, the FDR-C Blasting & Painting Dehumidifier contains three working modes: “summer mode”, “winter mode”, “general mode”. These seasonal working modes greatly help the end users carrying out blasting & painting regardless of weather.
Model No.
|
FDR-5-D
|
FDR-10-D
|
FDR-20-D
|
FDR-30-D
|
|||||
General Specification
|
Rated Air Flow
|
m3/h
|
500
|
1000
|
2000
|
3000
|
|||
Available space
|
m3
|
38
|
60
|
100
|
150
|
||||
Number of Personnel
|
--
|
2
|
4
|
7
|
|||||
Refrigeration Capacity
|
KW
|
30
|
46
|
65
|
82
|
||||
E.S.P
|
Pa
|
200~
|
200~
|
200~
|
200~
|
||||
1000
|
1000
|
1000
|
1000
|
||||||
Noise Level without duct
|
dB(A)
|
62
|
65
|
67
|
69
|
||||
Temperature Control Range & Accuracy
|
18~26℃±1℃
|
||||||||
Humidity Control Range & Accuracy
|
0.2~1%
|
||||||||
Power Source
|
3PH/380V/50HZ
|
||||||||
Dehumidification system
|
Wheel type
|
Silica Gel + Molecular Sieve
|
|||||||
Reactivation Heating System
|
Electrical Heating
|
KW
|
9
|
21
|
39
|
61
|
|||
Steam Heating
|
Kg/h
|
--
|
36
|
67
|
104
|
||||
Energy-saving Heating
|
KW
|
--
|
--
|
30
|
45
|
||||
Reactivation Fan Power
|
KW
|
0.18
|
0.37
|
0.75
|
1.1
|
||||
Refrigeration System
|
Compressor
|
Type
|
Hermetic
|
Hermetic
|
Hermetic
|
Hermetic
|
|||
Qty
|
Sets
|
2
|
2
|
2
|
2
|
||||
Power
|
KW
|
4.97×2
|
7.91×2
|
10.2×2
|
14×2
|
||||
Evaporator
|
Copper tube & Hydrophilic Aluminum Finned Type
|
||||||||
Refrigerant
|
Type
|
R22
|
|||||||
Throttle Governing
|
Thermal Expansion Valve
|
||||||||
Process Fan Power
|
KW
|
1.5
|
2.2
|
3
|
4
|
||||
Weight
|
Kg
|
1300
|
1800
|
2360
|
2780
|
||||
Dimension
|
mm
|
4300×1500×2200
|
5000×1700×2320
|
||||||
Remark
|
1.Rated working conditions:dry-bulb temperature33℃,wet-bulb temperature28℃;
2. Reactivation steam pressure:0.4Mpa; 3. Air velocity through desiccant wheel:2-4m/s; 4. Customized unit,large splited type available; 5. All content contained in this table may be subject to change without prior notice. |
||||||||
Model No.
|
FDR-50-D
|
FDR-75-D
|
FDR-100-D
|
FDR-150-D
|
||||||
General Specification
|
Rated Air Flow
|
m3/h
|
5000
|
7500
|
10000
|
15000
|
||||
Available space
|
m3
|
230
|
350
|
420
|
500
|
|||||
Number of Personnel
|
15
|
34
|
70
|
100
|
||||||
Refrigeration Capacity
|
KW
|
104
|
167
|
202
|
315
|
|||||
E.S.P
|
Pa
|
200~
|
200~
|
200~
|
200~
|
|||||
1000
|
1000
|
1000
|
1000
|
|||||||
Noise Level without duct
|
dB(A)
|
72
|
75
|
77
|
79
|
|||||
Temperature Control Range & Accuracy
|
18~26℃±1℃
|
|||||||||
Humidity Control Range & Accuracy
|
0.2~1%
|
|||||||||
Power Source
|
3PH/380V/50HZ
|
|||||||||
Dehumidification system
|
Wheel type
|
Silica Gel + Molecular Sieve
|
||||||||
Reactivation Heating System
|
Electrical Heating
|
KW
|
101
|
149
|
196
|
286
|
||||
Steam Heating
|
Kg/h
|
172
|
254
|
333
|
486
|
|||||
Energy-saving Heating
|
KW
|
76
|
112
|
147
|
206
|
|||||
Reactivation Fan Power
|
KW
|
1.5
|
2.2
|
3
|
5.5
|
|||||
Refrigeration System
|
Compressor
|
Type
|
Hermetic
|
Hermetic
|
Semi-Hermetic
|
Semi-Hermetic
|
||||
Qty
|
Sets
|
2
|
2
|
2
|
2
|
|||||
Power
|
KW
|
17.7×2
|
22×2
|
33×2
|
46.4×2
|
|||||
Evaporator
|
Copper tube & Hydrophilic Aluminum Finned Type
|
|||||||||
Refrigerant
|
Type
|
R26
|
||||||||
Throttle Governing
|
Thermal Expansion Valve
|
|||||||||
Process Fan Power
|
KW
|
5
|
7.5
|
13
|
15
|
|||||
Weight
|
Kg
|
3300
|
3960
|
4500
|
5200
|
|||||
Dimension
|
mm
|
5600×1860×2500
|
6500×2000×2650
|
|||||||
Remark
|
1.Rated working conditions:dry-bulb temperature33℃,wet-bulb temperature28℃;
2. Reactivation steam pressure:0.4Mpa; 3. Air velocity through desiccant wheel:2-4m/s; 4. Customized unit,large splited type available; 5. All content contained in this table may be subject to change without prior notice. |
|||||||||